4 Zone Expansion Unit
230VAC light switching unit with 1 Amp 12VDC p/s
Designed to work with the GJD DygiZone digital lighting controller and the GJD range of external PIR detectors, the 4 Zone Expansion Unit greatly simplifies installation time and cost.
The 4 Zone Expansion unit incorporates an energy efficient switched mode power supply and can control up to four individual lighting circuits each with 1500W resistive load.
Part Codes
GJD040 4 Zone Expansion Units
Gallery
.jpg)
|
Technical Specifications |
|
Supply |
2 x 230 VAC 50HZ via RCD, MCB and 13 amp Fused spurs.
|
|
Lighting Outputs |
4 x 230 VAC 50HZ 1500 watts maximum
|
|
Provides |
12VDC at 1A
|
|
'T' Outputs: (1 & 2 and 3 & 4) |
5mA +ve suitable for driving base of NPN Transistor
|
|
Aux Outputs: (1 & 2 and 3 & 4) |
50mA -ve suitable for driving low power sounders |
|
Cable Guide |
1.5mm twin & earth for mains cable
GJD Detectors:
200m - 7/0.2mm - 4 to 8 core
400m - 16/02mm - 4 to 8 core
Touch Controls:
200m - 7/0.2mm - 6 core screened (Max. 200m from first touch control to last Expansion Unit) |
|
Mounting |
Install indoors in a clean dry location on a secure flat surface |
|
Operating Temp |
-10°C to + 50°C. Conformally coated electronics for increased stability |
|